COMMERCIAL STEAM GENERATOR
EXECUTIVE SERIES (ES) WITH AUTO POWER FLUSH
INTRODUCTION TO STEAM GENERATOR FUNCTIONS This unit is designed and manufactured based on your specific
requirements. Each steam generator has it own function, which may
operate differently from another steam generator. This section explains
different functions on steam generators. Your unit may have some of
these functions. Read your order sheet to find out which functions your
unit has.
REGULAR 2-in-1 SYSTEM
The unit has two heating stages. When the thermostat is calling for heat,
both stages get engaged and produce strong steam until the temperature
SETPOINT is reached in the steam room. Then one stage, which is
controlled by thermostat, goes off and the other stage keeps on
producing steam (steady but slow).
SPECIAL 2-in-1 SYSTEM
This system also has two stages, but a separate thermostat controls each
stage individually. The SETPOINT for the top thermostat is slightly higher
than the bottom thermostat. When the lower SETPOINT in bottom
thermostat is reached, one stage goes off, but the other stage keeps on
steaming until the higher SETPOINT in top thermostat is reached.
STAND BY SYSTEM
The unit only produces steam on demand. When the user turns on the
30 minute mechanical or IN-ROOM-TOUCH timer the unit start
producing strong steam until one of the following happens:
• Timer times out (turns off)
• Temperature SETPOINT is reached
Then the unit stops producing steam and stands by for the next request.
Only the first heating cycle in the daily schedule will take about 10
minutes longer than the consequent next cycles to produce steam.
BINARY SETTING
The thermostat implements two different sets of SETPOINTS to control
the temperature in the steam room. The regular SETPOINT is about
117°F (47°C) and the secondary SETPOINT is less than by OFFSET value,
25°F (15°C):
Secondary SETPOINT= Regular SETPOINT – OFFSET Value
Secondary SETPOINT= 117°F – 25°F= 92°F
A mechanical timer or Electronic In-Room- Touch timer activates the
transition from Regular SETPOINT to Secondary SETPOINT and vice
versa.
|